ROCAS 261 AC
AC-coupled BESS
Integrated liquid-cooled battery and PCS cabinet with modular parallel expansion, rapid electrical protection, real-time monitoring and fault logging.
- Energy
- 261 kWh
- Power
- 125 kW
- Cell
- LFP 314 Ah
- Cooling
- Liquid
- Dimensions
- 1,000 × 1,350 × 2,300 mm
- Weight
- 2,670 kg
Download datasheetDiscuss this system
PDF, English, 432 KB
Technical specifications
AC / grid-connected
| Rated output | 125 kW |
|---|---|
| Overload | 1.1× continuous; 1.2× for 1 min |
| Rated voltage / wiring | 400 V (-15% to +10%); 3P+N+PE |
| Rated current | 180 A |
| Power factor | -1 to +1 |
| Grid frequency | 50/60 Hz ±2.5 Hz |
| THDI | ≤3% |
AC / off-grid
| Voltage | 400/380 V ±3% |
|---|---|
| Frequency | 50/60 Hz |
| THDU | <3% with linear load |
| Unbalanced load | 100% |
Battery
| Cell chemistry / rating | LFP; 3.2 V / 314 Ah |
|---|---|
| Configuration | 1P260S |
| Energy at 25°C / 0.5P | 261 kWh |
| DC range / nominal | 702–936 V / 832 V |
| Cycle life | 8,000 cycles (0.5P, 25 ±2°C, 70% SOH) |
System / environment
| Charge / discharge / display | ≤0.5P; optional touch screen |
|---|---|
| Dimensions W × D × H | 1,000 × 1,350 × 2,300 mm |
| Weight | 2,670 kg |
| Noise | <75 dB |
| Enclosure / battery pack | IP54 / IP67 |
| System efficiency | ≥88% |
| Ambient temperature | -20 to +55°C |
| Humidity | ≤95% |
| Cooling | Liquid cooling |
| Fire suppression | Aerosol |
| Communications | Ethernet / CAN / RS485 |
| Maximum altitude | 2,000 m |
| Standards* | GB/T 34120; GB/T 36276; IEC 62477; IEC 62619; IEC 61000; UN 38.3 |
Specifications are indicative and refer to the standard configuration. Final values, certificates and warranty terms are confirmed in the project-specific technical offer.
* Standards referenced in the product documentation. Model-specific conformity documents are provided for project review.
Product images are representative. Final appearance depends on the selected configuration.
Related systems
Other systems in the same range.
Discuss the ROCAS 261 AC for your site.
Power, capacity, site and timeline are enough to start. We reply with the right configuration and next steps.