ROCAS 215 AC
AC-coupled BESS
Pre-assembled liquid-cooled system with modular expansion, supporting grid-connected, off-grid and virtual power plant operating modes.
- Energy
- 215 kWh
- Power
- 100 kW
- Cell
- LFP 280 Ah
- Cooling
- Liquid
- Dimensions
- 1,000 × 1,350 × 2,300 mm
- Weight
- 2,400 kg
Download datasheetDiscuss this system
PDF, English, 431 KB
Technical specifications
AC / grid-connected
| Rated output | 100 kW |
|---|---|
| Overload | 1.1× continuous; 1.2× for 1 min |
| Rated voltage / wiring | 400 V (-15% to +10%); 3P+N+PE |
| Rated current | 145 A |
| Power factor | -1 to +1 |
| Grid frequency | 50/60 Hz ±2.5 Hz |
| THDI | ≤3% |
AC / off-grid
| Voltage | 400/380 V ±3% |
|---|---|
| Frequency | 50/60 Hz |
| THDU | <3% with linear load |
| Unbalanced load | 100% |
Battery
| Cell chemistry / rating | LFP; 3.2 V / 280 Ah |
|---|---|
| Configuration | 1P240S |
| Energy at 25°C / 0.5P | 215 kWh |
| DC range / nominal | 648–864 V / 768 V |
| Cycle life | 8,000 cycles (0.5P, 25 ±2°C, 70% SOH) |
System / environment
| Charge / discharge / display | ≤0.5P; optional touch screen |
|---|---|
| Dimensions W × D × H | 1,000 × 1,350 × 2,300 mm |
| Weight | 2,400 kg |
| Noise | <75 dB |
| Enclosure / battery pack | IP54 / IP67 |
| System efficiency | ≥88% |
| Ambient temperature | -20 to +55°C |
| Humidity | ≤95% |
| Cooling | Liquid cooling |
| Fire suppression | Aerosol |
| Communications | Ethernet / CAN / RS485 |
| Maximum altitude | 2,000 m |
| Standards* | GB/T 34120; GB/T 36276; IEC 62477; IEC 62619; IEC 61000; IEC 63056; UN 38.3 |
Specifications are indicative and refer to the standard configuration. Final values, certificates and warranty terms are confirmed in the project-specific technical offer.
* Standards referenced in the product documentation. Model-specific conformity documents are provided for project review.
Product images are representative. Final appearance depends on the selected configuration.
Related systems
Other systems in the same range.
Discuss the ROCAS 215 AC for your site.
Power, capacity, site and timeline are enough to start. We reply with the right configuration and next steps.